Pair: 1 - 20
Cross-Section: 0,80 mm2

J-SH(St)SH FE 180 E30/E90

Application

These cables fields of use as a control,data and power supply cable they are fire proof and halogen free cables which, on the basis of a fixed operating mode, can continue with the supply of a power for a period of 30-180 minutes under the existing fire conditions (at a temperature of 750 °C and under the flames). Because of their unique features, they can be used; on the fire alarm systems, on the equipment and devices which are connected to the fire alarm devices, in the environments which have no corrosive gases are emitted in the event of fire.

Cable design Tehnical data
Conductor    : Plain Cu conductor solid.
Insulation : Silicone rubber compound.
Core identification : VDE 0815
Pair : Two conductors twisted to a pair.
Lay-up : Pairs laid up in layers of optimum pitch.
Seperator : Polyester band
screen : With drain wire under the aluminium foil.
Outer Sheath : Flame and heat resistant sheath material of halogen-free silicone rubber compound.
Sheath Colour : Orange
It has Ex-proof & FE 180 certification
Standard : According to VDE 0815.
Insulation resistance : > 100 Mohm.km    
Mutual capacitance : 120 nF/km
Operating voltage : 300 V
Test voltage (AC 50 Hz) : 800 V
Temperature range : -60 °C / +180 °C
Min. Bending radius : 7,5 x Cable diameter
Flame test : IEC 332-1 & IEC 332-3
Insulation integrity (FE 180) : IEC 331 (TS 3164 Ex-Proof)