Pair: 2 - 36
Cross-Section: 0,50 mm2 - 2,5 mm2
Pair: 2 - 4
Cross-Section: 4 mm2 - 50 mm2
Cables | Silicone cables

SİMH - FR / FE 180

Application

These cables fields of use as a control and power supply cable they are fire proof and halogen free cables which, on the basis of a fixed operating mode, can continue with the supply of a power for a period of 30-180 minutes under the existing fire conditions (at a temperature of 750 °C and under the flames). Because of their unique features, they can be used; on the fire alarm systems, on the equipment and devices which are connected to the fire alarm devices, in the environments which have no corrosive gases are emitted in the event of fire. These cables are used at schools, airpots, hospitals, etc.

Cable design Tehnical data
Conductor    : Plain Cu wires, flexible acording to IEC 228-5.
Insulation : Silicone rubber compound.
Core identification : According to VDE 0293-308.
Lay-up : Cores laid up in layers of optimum pitch.
Outer Sheath : Flame and heat resistant sheath material of halogen-free silicone rubber compound.
Sheath Colour : Orange
It has Ex-proof & FE 180 certification
Standard : VDE 0250
Insulation resistance : > 20 Mohm.km    
Rated voltage Uo/U : 300 / 500 V
Test voltage (AC 50 Hz) : 2000 V
Temperature range : -60 °C / +180 °C
Min. Bending radius : 7,5 x Cable diameter
Flame test : IEC 332-1 & IEC 332-3
Insulation integrity (FE 180) : IEC 331 (TS 3164 Ex-Proof)