PVC Insulated, Non-Sheadted Single Core Cable With Copper Conductor

1
 
 
 

Code
H05V-U, H07V-U, H07V-R (NYA), CU/PVC
U: Solid Conductor. R: Stranded Conductor.

Standards
TS 9758, VDE 0281, IEC 60227, BS 6004, HD 21.3 S3

Technical Data
Max.operating temperature : 70 ° C
Short circuit temperature : 160 ° C (max. 5 sec.)
Rated voltage : 300/500 V, 450/750 V

Application
In dry rooms, switch and distribution boards, for laying in conduit on and under plaster and on insulating supports above plaster.

Construction
1. Solid or stranded copper conductor.
2. PVC insulation.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

Current carrying capacity
In ground at 20 ° C
In Air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

A

A

0.5re *

2.1

8

100

36.0

-

9

0.75re *

2.3

11

100

24.5

-

15

1 .0 re *

2.5

14

100

18.1

11

19

1.5re

2.8

20

100

12.1

15

24

2.5re

3.3

31

100

7.41

20

32

4re

3.8

46

100

4.61

25

42

6re

4.3

54

100

3.08

33

54

1Ore

5.6

108

100

1.83

45

73

10rm

6.0

111

100

1.83

45

73

16rm

7.0

170

1000

1.15

61

98

25rm

8.5

260

1000

0.727

83

129

35rm

9.5

355

1000

0.524

103

158

50rm

11.0

505

1000

0.387

132

198

70rm

13.0

694

1000

0.268

165

245

95rm

15.0

938

1000

0.193

197

292

120rm

16.5

1172

1000

0.153

235

344

150rm

18.0

1465

1000

0.124

-

391

185rm

20.0

1808

1000

0.0991

-

448

240rm

23.0

2343

1000

0.0754

-

528

300rm

26.0

2921

1000

0.0601

-

608

400rm

29.5

3875

1000

0.0470

-

726
re: Solid conductor
rm:
Stranded conductor
* 300/500V H05V-U