Cables | Energy cables | Low voltage cables

PVC Insulated, Single Core Cables With Copper Conductor

1

0.6/1 kV

 
 

Code
YVV-U, YVV-R, CU/PVC/PV, NYY
U:Solid conductor
R:Stranded conductor

Standards
TS IEC 60502, VDE 0276

Technical Data
Max. operating temperature : 70 ° C
Max. short circuit temperature : (max. 5 sec.)
Cross section < 300 mm : 160 ° C
Cross section > 300 mm : 140 ° C
Rated voltage : 0.6/1 kV
Min. bending radius : 15 x D
D : Cable outer diameter

Application
Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.

Construction
1. Solid or stranded copper conductor.
2. PVC insulation.
3. PVC filler.
4. PVC outer sheath.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

Capacity in ground at 30 ° C
Capacity in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

1x1,5

5.8

50

1000

12.1000

-

-

25

20

1x2,5

6.2

60

1000

7.4100

-

-

34

27

1x4

7.0

85

1000

4.6100

-

-

45

37

1x6

7.5

105

1000

3.0800

-

-

57

48

1x10

9.0

160

1000

1.8300

-

-

78

66

1x16

10.0

215

1000

1.1500

127

107

103

89

1x25

11.5

320

1000

0.7270

163

137

137

118

1x35

12.5

420

1000

0.5240

195

165

169

145

1x50

14.0

570

1000

0.3870

230

195

206

176

1x70

15.5

780

1000

0.2680

282

239

261

224

1x95

18.0

1050

1000

0.1930

336

287

321

271

1x120

19.5

1300

1000

0.1530

382

326

374

314

1x150

21.0

1600

1000

0.1240

428

366

428

361

1x185

23.5

1950

1000

0.0991

483

414

494

412

1x240

27.0

2550

1000

0.0754

561

481

590

484

1x300

30.5

3150

1000

0.0601

632

542

678

549

1x400

34.0

4200

1000

0.0470

730

624

817

657

1x500

39.0

5200

1000

0.0366

823

698

940

749

1x630

42.0

6450

500

0.0283

866

775

1108

920

re:
rm: