Cables | Energy cables | Low voltage cables

PVC Insulated, Multi-Core Cables With Copper Conductor

1

0.6/1 kV

 
 

Code
YVV-U, YVV-R, CU/PVC/PVC, NYY
U:Solid conductor
R:Stranded conductor

Standards
TS IEC 60502, VDE 0276

Technical Data
Max. operating temperature : 70 ° C
Max. short circuit temperature : (max. 5 sec.)
Cross section < 300 mm : 160 ° C
Cross section > 300 mm : 140 ° C
Rated voltage : 0.6/1 kV
Min. bending radius : 12 x D
D : Cable outer diameter

Application
Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.

Construction
1. Solid or stranded copper conductor.
2. PVC insulation.
3. Filler.
4. PVC outer sheath.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

Capacity in ground at 30 ° C
Capacity in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

A
A

3x1,5

12.0

200

1000

12.1000

26

18.5

3x2,5

13.0

250

1000

7.4100

34

25

3x4

14.5

340

1000

4.6100

44

34

3x6

15.5

425

1000

3.0800

56

43

3x10

18.5

620

1000

1.8300

75

60

3x16

20.5

835

1000

1.1500

98

80

3x25

24.0

1250

1000

0.7270

128

106

3x35

26.0

1600

1000

0.5240

157

131

3x50

29.5

2100

1000

0.3870

185

159

3x70

33.5

2900

1000

0.2680

228

202

3x95

38.0

3900

1000

0.1930

275

244

3x120

42.0

4800

1000

0.1530

313

282

3x150

46.0

5900

500

0.1240

353

324

3x185

51.0

7300

500

0.0991

399

371

3x240

58.0

9450

500

0.0754

464

436

3x300

65.0

11800

250

0.0601

524

481

3x400

71.0

15500

250

0.0470

600

560