Cables | Energy cables | Low voltage cables

PVC Insulated, Multi-Core Cables With Copper Conductor

1

0.6/1 kV

 
 

Code
YVV-U, YVV-R, CU/PVC/PVC, NYY
U:Solid conductor
R:Stranded conductor

Standards
TS IEC 60502, VDE 0276

Technical Data
Max. operating temperature : 70 ° C
Max. short circuit temperature : (max. 5 sec.)
Cross section < 300 mm : 160 ° C
Cross section > 300 mm : 140 ° C
Rated voltage : 0.6/1 kV
Min. bending radius : 12 x D
D : Cable outer diameter

Application
Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.

Construction
1. Solid or stranded copper conductor.
2. PVC insulation.
3. Filler.
4. PVC outer sheath.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

in ground at 30 ° C
in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

A
A

4x1,5

12.5

235

1000

12.1000

26

18.5

4x2,5

13.5

300

1000

7.4100

34

25

4x4

15.5

400

1000

4.6100

44

34

4x6

17.0

520

1000

3.0800

56

43

4x10

20.0

765

1000

1.8300

75

60

4x16

22.5

1050

1000

1.1500

98

80

4x25

26.0

1550

1000

0.7270

128

106

4x35

28.5

2000

1000

0.5240

157

131

4x50

33.0

2750

1000

0.3870

185

159

4x70

37.5

3750

1000

0.2680

228

202

4x95

42.5

5000

1000

0.1930

275

244

4x120

46.5

6200

500

0.1530

313

282

4x150

51.5

7600

500

0.1240

353

324

4x185

57.0

9450

500

0.0991

399

371

4x240

65.0

12200

500

0.0754

464

436

4x300

73.0

15200

250

0.0601

524

481

4x400

79.0

19500

250

0.0470

600

560