Cables | Energy cables | Low voltage cables

PVC Insulated, Round Steel Wire Armoured, Multi-Core Cables With Copper Conductor

1

0.6/1 kV

 
 

Code
YVZ2V-U, YVZ2V-R, CU/PVC/SWA/PVC, NYRY
U:Solid conductor
R:Stranded conductor

Standards
TS IEC 60502, VDE 0271, BS 6346

Technical Data
Max. operating temperature          : 70"C
Max. short circuit temperature      : (max. 5 sec.)
Cross section < 300 mm               : 160°C
Cross section > 300 mm               : 140°C
Rated voltage                                : 0.6/1 kV
Min. bending radius                       : 12 x D
D                                                    : Cable outer diameter

Application
Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.

Construction
1. Solid or stranded copper conductor.
2.PVC insulation.
3.Filler.
4.Galvanized round steel wires.
5.Polyester tape.
6. PVC outer sheath.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

Curent carrying capacity
in ground at 20 ° C
in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

A
A

4x1,5

15.0

400

1000

12.1

26

18.5

4x2,5

15.5

480

1000

7.41

34

25

4x4

18.5

770

1000

4.61

44

34

4x6

20.0

900

1000

3.08

56

43

4x10

23.0

1200

1000

1.83

75

60

4x16

26.0

1700

1000

1.15

98

80

4x25

29.5

2300

1000

0.727

128

106

4x35

32.5

2870

1000

0.524

157

131

4x50

37.5

4000

1000

0.387

185

159

4x70

41.5

5150

500

0.268

228

202

4x95

48.0

7050

500

0.193

275

244

4x120

52.5

8450

500

0.153

313

282

4x150

57.0

10050

250

0.124

353

324

4x185

63.0

12150

250

0.0991

399

371

4x240

70.5

15300

250

0.0754

464

436

4x300

79.0

18700

250

0.0601

524

481

4x400

90.0

25000

250

0.0470

600

560