Cables | Energy cables | Low voltage cables

PVC Insulated, Round Steel Wire Armoured, Control Cables With Copper Conductor

1

0.6/1 kV

 
 

Code
YVZ2V-U, YVZ2V-R, CU/PVC/SWA/PVC, NYRY U
U:Solid conductor
R:Stranded conductor

Standards
TS IEC 60502, VDE 0271, BS 6346

Technical Data
Max. operating temperature          : 70°C
Max. short circuit temperature      : 160°C (max. 5 sec.)
Rated voltage                                : 0.6/1 kV
Min. bending radius                       : 12 x D
D                                                    : Cable outer diameter

Application
Used as control cable, indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.

Construction
1. Solid or stranded copper conductor.
2.PVC insulation.
3.Filler.
4.Galvanized round steel wires.
5.Polyester tape.
6.PVC outer sheath.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

Curent arrying capacity
in ground at 20 ° C
in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

A
A

5x2,5

16.5

550

1000

7.41

23.8

18.8

6x2,5

18.5

750

1000

7.41

22.1

17.5

7x2,5

19.0

760

1000

7.41

20.4

16.3

8x2,5

20.0

880

1000

7.41

18.7

15.0

10x2,5

22.0

1050

1000

7.41

17.0

13.8

12x2,5

22.5

1100

1000

7.41

16.2

13.1

14x2,5

24.0

1350

1000

7.41

15.3

12.5

16x2,5

25.0

1500

1000

7.41

14.5

11.9

19x2,5

26.0

1600

1000

7.41

13.6

11.3

21x2,5

27.0

1750

1000

7.41

12.9

10.8

24x2,5

29.5

2000

1000

7.41

11.9

10.0

27x2,5

30.0

2100

1000

7.41

11.6

9.7

30x2,5

31.0

2250

1000

7.41

11.2

9.4

37x2,5

33.0

2600

1000

7.41

10.6

9.1

40x2,5

35.0

3000

1000

7.41

10.2

8.8

48x2,5

38.5

3550

1000

7.41

9.5

8.3

52x2,5

39.5

3700

1000

7.41

8.9

7.8

61x2,5

41.5

4150

1000

7.41

8.5

7.5