Cables | Energy cables | Low voltage cables

PVC Insulated, Double Steel Tape Armoured, Multi-Core Cables With Copper Conductor

1

0.6/1 kV

 
 

Code
YVZ4V-U, YVZ4V-R, CU/PVC/STA/PVC, NYBY
U:Solid conductor
R:Stranded conductor

Standards
TS IEC 60502, VDE0271

Technical Data
Max. operating temperature          : 70°C
Max. short circuit temperature      : (max. 5 sec.)
Cross section < 300 mm               : 160°C
Cross section > 300 mm               : 140°C
Rated voltage                                : 0.6/1 kV
Min. bending radius                       : 12 x D
D                                                    : Cable outer diameter

Application
Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is risk of mechanical damage.

Construction
1. Solid or stranded copper conductor.
2. PVC insulation.
3. Filler.
4. Galvanized double steel tape armoured.
5. PVC outer sheath.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

Curent carrying capacity
in ground at 20 ° C
in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

A
A

4x1,5

14.0

360

1000

12.1

26

18.5

4x2,5

15.0

440

1000

7.41

34

25

4x4

17.0

580

1000

4.61

44

34

4x6

18.0

700

1000

3.08

56

43

4x10

21.0

980

1000

1.83

75

60

4x16

23.5

1300

1000

1.15

98

80

4x25

27.0

1850

1000

0.727

128

106

4x35

29.5

2350

1000

0.524

157

131

4x50

34.0

3100

1000

0.387

185

159

4x70

39.0

4450

1000

0.268

228

202

4x95

44.5

5800

500

0.193

275

244

4x120

49.0

7100

500

0.153

313

282

4x150

53.5

8600

500

0.124

353

324

4x185

59.0

10500

250

0.0991

399

371

4x240

67.0

13400

250

0.0754

464

436

4x300

75.5

16600

250

0.0601

524

481

4x400

85.5

21650

250

0.0470

600

560