Cables | Energy cables | Low voltage cables

PVC Insulated, Flat Steel Wire Armoured, Multi-Core Cables With Copper Conductor

1

0.6/1 kV

 
 

Code
YVZ3V-R, CU/PVC/SWA/PVC, NYFGbY
R:Stranded conductor

Standards
TS IEC 60502, VDE0271

Technical Data
Max. operating temperature          : 70"C
Max. short circuit temperature      : (max. 5 sec.)
Cross section < 300 mm               : 160°C
Cross section > 300 mm               : 140°C
Rated voltage                                : 0.6/1 kV
Min. bending radius                       : 12 x D
D                                                    : Cable outer diameter

Application
Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is risk of mechanical damage.

Construction
1. Stranded copper conductor.
2. PVC insulation.
3. Filler.
4. Galvanized flat steel wire.
5. Galvanized steel binding tape.
6. PVC outer sheath.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

Curent carrying capacity
in ground at 20 ° C in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

A
A

4x10

22.0

1150

1000

1.83

75

60

4x16
24.5
1500
1000
1.15
98
80

4x25

28.0

2050

1000

0.727

128

106

4x35
31.0
2600
1000
0.524
157
131
4x50
35.0
3450
1000
0.387
185
159
4x70
39.5
4500
1000
0.268
228
202

4x95

45.0

5850

500

0.193

275

244

4x120

49.0

7150

500

0.153

313

282

4x150
54.0
8700
500
0.124
353
324

4x185

59.5

10650

500

0.0991

399

371

4x240

67.0

13550

250

0.0754

464

436

4x300
76.0
16750
250
0.0601
524
481

4x400

85.5

21850

250

0.0470

600

560