Cables | Energy cables | Low voltage cables | |
PVC Insulated, Flat Steel Wire Armoured, Multi-Core Cables With Copper Conductor |
|
1 | |
0.6/1 kV |
|
Code Standards Max. operating temperature : 70"C Max. short circuit temperature : (max. 5 sec.) Cross section < 300 mm : 160°C Cross section > 300 mm : 140°C Rated voltage : 0.6/1 kV Min. bending radius : 12 x D D : Cable outer diameter Application 1. Stranded copper conductor. 2. PVC insulation. 3. Filler. 4. Galvanized flat steel wire. 5. Galvanized steel binding tape. 6. PVC outer sheath. |
DIMENSIONS AND WEIGHTS |
ELECTRICAL PROPERTIES |
|||||
Nominal |
Overall Diameter (approx.) |
Net Weight (approx.) |
Delivery Lenght |
DC Conductor Resistance at 20 ° C |
Curent carrying capacity |
|
in ground at 20 ° C | in air at 30 ° C | |||||
mm 2 |
mm |
kg/km |
m |
ohm/km |
A |
A |
3x16+10 |
24.0 |
1450 |
1000 |
1.15 |
98 |
80 |
3x25+16 |
27.5 |
2000 |
1000 |
0.727 |
128 |
106 |
3x35+16 |
29.5 |
2300 |
1000 |
0.524 |
157 |
131 |
3x50+25 |
33.5 |
3050 |
1000 |
0.387 |
185 |
159 |
3x70+35 |
37.5 |
4000 |
1000 |
0.268 |
228 |
202 |
3x95+50 |
43.0 |
5250 |
1000 |
0.193 |
275 |
244 |
3x120+70 |
47.5 |
6500 |
500 |
0.153 |
313 |
282 |
3x150+70 |
50.5 |
7600 |
500 |
0.124 |
353 |
324 |
3x185+95 |
56.0 |
9400 |
500 |
0.0991 |
399 |
371 |
3x240+120 |
63.0 |
11900 |
250 |
0.0754 |
464 |
436 |
3x300+150 |
70.0 |
14600 |
250 |
0.0601 |
524 |
481 |
3x400+185 |
79.0 |
18900 |
250 |
0.0470 |
600 |
560 |