Cables | Energy cables | Low voltage cables

PVC Insulated, Flat Steel Wire Armoured, Multi-Core Cables With Copper Conductor

1

0.6/1 kV

 
 

Code
YVZ3V-R, CU/PVC/SWA/PVC, NYFGbY
R:Stranded conductor

Standards
TS IEC 60502, VDE0271

Technical Data
Max. operating temperature          : 70"C
Max. short circuit temperature      : (max. 5 sec.)
Cross section < 300 mm               : 160°C
Cross section > 300 mm               : 140°C
Rated voltage                                : 0.6/1 kV
Min. bending radius                       : 12 x D
D                                                    : Cable outer diameter

Application
Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is risk of mechanical damage.

Construction
1. Stranded copper conductor.
2. PVC insulation.
3. Filler.
4. Galvanized flat steel wire.
5. Galvanized steel binding tape.
6. PVC outer sheath.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

Curent carrying capacity
in ground at 20 ° C in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

A
A

3x16+10

24.0

1450

1000

1.15

98

80

3x25+16

27.5

2000

1000

0.727

128

106

3x35+16

29.5

2300

1000

0.524

157

131

3x50+25

33.5

3050

1000

0.387

185

159

3x70+35

37.5

4000

1000

0.268

228

202

3x95+50

43.0

5250

1000

0.193

275

244

3x120+70

47.5

6500

500

0.153

313

282

3x150+70

50.5

7600

500

0.124

353

324

3x185+95

56.0

9400

500

0.0991

399

371

3x240+120

63.0

11900

250

0.0754

464

436

3x300+150

70.0

14600

250

0.0601

524

481

3x400+185

79.0

18900

250

0.0470

600

560