Cables | Energy cables | Low voltage cables

XLPE Insulated, Multi-Core Cables With Copper Conductor

1

0.6/1 kV

 
 

Code
YXV-U, YXV-R, CU/XLPE/PVC, N2XY
U: Solid conductor
R: Stranded conductor

Standards
TS IEC 60502, VDE0276

Technical Data
Max. operating temperature          : 90°C
Max. short circuit temperature      : 250°C (max. 5 sec.)
Rated voltage                                : 0.6/1 kV
Min. bending radius                       : 12 x D
D                                                    : Cable outer diameter


Application
These cables have a low dielectric loss, used in indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.

Construction
1. Solid or stranded copper conductor.
2. XLPE insulation.
3. Filler.
4. PVC outer sheath.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

Capacity in ground at 20 ° C
Capacity in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

A
A

3x1,5

11.5

180

1000

12.1

30

24

3x2,5

12.5

230

1000

7.41

40

32

3x4

13.5

300

1000

4.61

52

42

3x6

14.5

370

1000

3.08

64

53

3x10

17.0

550

1000

1.83

86

73

3x16

19.0

700

1000

1.15

111

96

3x25

22.5

1150

1000

0.727

143

130

3x35

24.5

1500

1000

0.524

173

160

3x50

27.5

1950

1000

0.387

205

195

3x70

32.0

2750

1000

0.268

252

247

3x95

36.0

3600

1000

0.193

303

305

3x120

40.0

4500

1000

0.153

346

355

3x150

44.5

5600

500

0.124

390

407

3x185

49.0

6950

500

0.0991

441

469

3x240

56.0

9000

500

0.0754

511

551

3x300

63.0

11200

250

0.0601

580

638

3x400

72.0

14750

250

0.0470

663

746