Cables | Energy cables | Low voltage cables

XLPE Insulated, Multi-Core Cables With Copper Conductor

1

0.6/1 kV

 
 

Code
YXV-R, CU/XLPE/PVC, N2XY
R: Stranded conductor

Standards
TS IEC 60502, VDE0276

Technical Data
Max. operating temperature          : 90°C
Max. short circuit temperature      : 250°C (max. 5 sec.)
Rated voltage                                : 0.6/1 kV
Min. bending radius                       : 12 x D
D                                                    : Cable outer diameter


Application
These cables have a low dielectric loss, used in indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.

Construction
1. Stranded copper conductor.
2. XLPE insulation.
3. Filler.
4. PVC outer sheath.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

Curent carrying capacity
in ground at 20 ° C
in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

A
A

4x1,5

12.0

200

1000

12.1

30

24

4x2,5

13.0

250

1000

7.41

40

32

4x4

14.5

350

1000

4.61

52

42

4x6

15.5

450

1000

3.08

64

53

4x10

18.5

700

1000

1.83

86

73

4x16

20.5

950

1000

1.15

111

96

4x25

24.5

1400

1000

0.727

143

130

4x35

27.0

1850

1000

0.524

173

160

4x50

30.5

2500

1000

0.387

205

195

4x70

35.5

3500

1000

0.268

252

247

4x95

39.5

4650

1000

0.193

303

305

4x120

44.5

5900

500

0.153

346

355

4x150

49.0

7200

500

0.124

390

407

4x185

54.5

8950

500

0.0991

441

469

4x240

62.0

11600

250

0.0754

511

551

4x300

70.0

14400

250

0.0601

580

638

4x400

80.0

19000

250

0.0470

663

746