Cables | Energy cables | Low voltage cables

XLPE Insulated, Multi-Core Cables With Copper Conductor

1

0.6/1 kV

 
 

Code
YXV-R, CU/XLPE/PVC, N2XY
R: Stranded conductor

Standards
TS IEC 60502, VDE0276

Technical Data
Max. operating temperature          : 90°C
Max. short circuit temperature      : 250°C (max. 5 sec.)
Rated voltage                                : 0.6/1 kV
Min. bending radius                       : 12 x D
D                                                    : Cable outer diameter


Application
These cables have a low dielectric loss, used in indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.

Construction
1. Stranded copper conductor.
2. XLPE insulation.
3. Filler.
4. PVC outer sheath.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

Curent carrying capacity
in ground at 20 ° C
in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

A
A

3x16+10

20.0

850

1000

1.15

111

96

3x25+16

23.5

1300

1000

0.727

143

130

3x35+16

25.5

1650

1000

0.524

173

160

3x50+25

29.0

2200

1000

0.387

205

195

3x70+35

33.5

3100

1000

0.268

252

247

3x95+50

37.5

4100

1000

0.193

303

305

3x120+70

42.0

5200

500

0.153

346

355

3x150+70

45.5

6250

500

0.124

390

407

3x185+95

51.0

7800

500

0.0991

441

469

3x240+120

58.0

10100

500

0.0754

511

551

3x300+150

65.0

12500

250

0.0601

580

638

3x400+185

73.5

16300

250

0.0470

663

746