Cables | Energy cables | Low voltage cables

XLPE Insulated, Round Steel Wire Armoured, Multi-Core Cables With Copper Conductor

1

0.6/1 kV

 
 

Code
YXZ2V-U, YXZ2V-R, CU/XLPE/SWA/PVC, N2XRY
U: Solid conductor
R: Stranded conductor

Standards
TS IEC 60502, BS 5467

Technical Data
Max. operating temperature          : 90°C
Max. short circuit temperature      : 250°C (max. 5 sec.)
Rated voltage                                : 0.6/1 kV
Min. bending radius                       : 12 x D
D                                                    : Cable outer diameter


Application
These cables have a low dielectric loss, used in indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is risk of mechanical damage.

Construction
1. Solid or stranded copper conductor.
2. XLPE insulation.
3. Filler.
4. Galvanized round steel wires.
5. Polyester tape.
6. PVC outer sheath.

 

 

 

 

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

Capacity in ground at 20 ° C
Capacity in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

A
A

3x1,5

13.5

330

1000

12.1

30

24

3x2,5

14.0

390

1000

7.41

40

32

3x4

15.5

470

1000

4.61

52

42

3x6

16.5
550
1000
3.08

64

53

3x10

20.0

950

1000

1.83

86

73

3x16

22.0

1200

1000

1.15

111

96

3x25

26.0

1800

1000

0.727

143

130

3x35

28.0

2200

1000

0.524

173

160

3x50

31.0

2800

1000

0.387

205

195

3x70

36.5

4000

1000

0.268

252

247

3x95

40.5

5000

500

0.193

303

305

3x120

44.5

6050

500

0.153

346

355

3x150

50.0

7750

500

0.124

390

407

3x185

55.0

9300

500

0.0991

441

469

3x240

61.5

11650

250

0.0754

511

551

3x300

69.0

14000

250

0.0601

580

638

3x400

77.0

18000

250

0.0470

663

746