Cables | Energy cables | Low voltage cables

XLPE Insulated, Round Steel Wire Armoured, Multi-Core Cables With Copper Conductor

1

0.6/1 kV

 
 

Code
YXZ2V-R, CU/XLPE/SWA/PVC, N2XRY
R: Stranded conductor

Standards
TS IEC 60502, BS 5467

Technical Data
Max. operating temperature          : 90°C
Max. short circuit temperature      : 250°C (max. 5 sec.)
Rated voltage                                : 0.6/1 kV
Min. bending radius                       : 12 x D
D                                                    : Cable outer diameter


Application
These cables have a low dielectric loss, used in indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is risk of mechanical damage.

Construction
1. Solid or stranded copper conductor.
2. XLPE insulation.
3. Filler.
4. Galvanized round steel wires.
5. Polyester tape.
6. PVC outer sheath.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

Curent carrying capacity
in ground at 20 ° C
in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

A
A

4x1,5

14.0

380

1000

12.1

30

24

4x2,5

15.0

440

1000

7.41

40

32

4x4

16.0

550

1000

4.61

52

42

4x6

18.5

800

1000

3.08

64

53

4x10

21.0

1100

1000

1.83

86

73

4x16

24.0

1550

1000

1.15

111

96

4x25

28.0

2150

1000

0.727

143

130

4x35

30.5

2700

1000

0.524

173

160

4x50

34.0

3400

1000

0.387

205

195

4x70

40.0

4850

1000

0.268

252

247

4x95

44.0

6150

500

0.193

303

305

4x120

50.5

8000

500

0.153

346

355

4x150

55.0

9600

500

0.124

390

407

4x185

60.5

11570

250

0.0991

441

469

4x240

68.0

14550

250

0.0754

511

551

4x300

76.0

17750

250

0.0601

580

638

4x400

87.0

23800

200

0.0470

663

746