Cables | Energy cables | Low voltage cables

XLPE Insulated, Round Steel Wire Armoured, Multi-Core Cables With Copper Conductor

1

0.6/1 kV

 
 

Code
YXZ2V-R, CU/XLPE/SWA/PVC, N2XRY
R: Stranded conductor

Standards
TS IEC 60502, BS 5467

Technical Data
Max. operating temperature          : 90°C
Max. short circuit temperature      : 250°C (max. 5 sec.)
Rated voltage                                : 0.6/1 kV
Min. bending radius                       : 12 x D
D                                                    : Cable outer diameter


Application
These cables have a low dielectric loss, used in indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is risk of mechanical damage.

Construction
1. Solid or stranded copper conductor.
2. XLPE insulation.
3. Filler.
4. Galvanized round steel wires.
5. Polyester tape.
6. PVC outer sheath.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

Curent carrying capacity
in ground at 20 ° C
in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

A
A

3x16+10

23.0

1300

1000

1.15

111

96

3x25+16

27.0

2000

1000

0.727

143

130

3x35+16

29.0

2350

1000

0.524

173

160

3x50+25

32.5

3100

1000

0.387

205

195

3x70+35

38.0

4400

1000

0.268

252

247

3x95+50

42.0

5500

500

0.193

303

305

3x120+70

46.5

6850

500

0.153

346

355

3x150+70

51.5

8450

500

0.124

390

407

3x185+95

56.5

10300

250

0.0991

441

469

3x240+120

63.5

12850

250

0.0754

511

551

3x300+150

70.5

15600

250

0.0601

580

638

3x400+185

80.0

20750

250

0.0470

663

746