Cables | Energy cables | Low voltage cables

XLPE Insulated, Round Steel Wire Armoured, Control Cables With Copper Conductor

1

0.6/1 kV

 
 

Code
YXZ2V-U, YXZ2V-R, CU/XLPE/SWA/PVC, N2XRY
U: Solid conductor
R: Stranded conductor

Standards
TS IEC 60502, BS 5467

Technical Data
Max. operating temperature          : 90°C
Max. short circuit temperature      : 250°C (max. 5 sec.)
Rated voltage                                : 0.6/1 kV
Min. bending radius                       : 12 x D
D                                                    : Cable outer diameter


Application
These cables have a low dielectric loss, used as control cable, indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is risk of mechanical damage.

Construction
1. Solid or stranded copper conductor.
2. XLPE insulation.
3. Filler.
4. Galvanized round steel wires.
5. Polyester tape.
6. PVC outer sheath.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

Current carrying capacity
in ground at 20 ° C in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

A
A

5x1,5

15.0

420

1000

12.1

21.0

18.0

6x1,5

15.5

470

1000

12.1

19.5

16.8

7x1,5

15.5

480

1000

12.1

18.0

15.6

8x1,5

18.0

670

1000

12.1

16.5

14.4

10x1,5

19.5

800

1000

12.1

15.0

13.2

12x1,5

20.0

850

1000

12.1

14.3

12.6

14x1,5

20.5

900

1000

12.1

13.5

12.0

16x1,5

21.5

950

1000

12.1

12.8

11.4

19x1,5

22.0

1050

1000

12.1

12.0

10.8

21x1,5

24.0

1300

1000

12.1

11.3

10.2

24x1,5

25.5

1450

1000

12.1

10.5

9.6

27x1,5

26.0

1500

1000

12.1

10.2

9.4

30x1,5

27.0

1600

1000

12.1

9.9

9.1

37x1,5

28.5

1800

1000

12.1

9.3

8.6

40x1,5

29.5

1950

1000

12.1

9.0

8.4

48x1,5

32.0

2250

1000

12.1

8.4

7.9

52x1,5

32.5

2350

1000

12.1

7.8

7.4

61x1,5

35.5

2900

1000

12.1

7.5

7.2