Cables | Energy cables | Low voltage cables

PVC Insulated, Multi-Core Cables With Aluminium Conductor

1

0.6/1 kV

 
 

Code
YAVV-R, AL/PVC/PVC, NAYY
R: Stranded conductor

Standards
TS IEC 60502, VDE 0276

Technical Data
Max. operating temperature          : 70°C
Max. short circuit temperature      : (max. 5 sec.)
Cross section < 300 mm               : 160°C
Cross section > 300 mm               : 140°C
Rated voltage                                : 0.6/1 kV
Min. bending radius                       : 12 x D
D                                                    : Cable outer diameter

Application
Indoors and outdoors, in cable ducts, underground, in power or switching stations, local energy distributions, industrial plants, where there is no risk of mechanical damage.

Construction
1. Stranded aluminium conductor.
2. PVC insulation.
3. Filler.
4. PVC outer sheath.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght

DC Conductor Resistance at 20 ° C

Current carrying capacity
in ground at 20 ° C
in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

A
A

3x35

26.5

930

1000

0.8680

118

102

3x50

30.5

1250

1000

0.6410

142

124

3x70

34.5

1650

1000

0.4430

176

158

3x95

39.5

2150

1000

0.3200

211

190

3x120

43.0

2550

1000

0.2530

242

221

3x150

48.0

3200

1000

0.2060

270

252

3x185

52.5

3900

1000

0.1640

308

289

3x240

59.5

4950

500

0.1250

363

339

3x300

65.5

6050

500

0.1000

412

377

3x400

74.0

7850

500

0.0778

475

444