Cables | Energy cables | Intermediate voltage cables

XLPE Insulated, Three Core Cables With Copper Conductor

1

3.6/6 kV

 
 
1

Code
YXC8V-R, N2XSEY, CU/XLPE/CTS/PVC
R:Stranded conductor

Standards
TS IEC 60502, BS 6622, VDE 0276

Technical Data
Max. operating temperature : 90 ° C
Max. short circuit temperature: 250 ° C (max. 5 sec.)
Rated voltage : 3.6/6 kV
Min. bending radius : 15 x D
D : Cable outer diameter

Application
These are cables with low dielectric losses used in energy networks with sudden load changes. Laid in residential or industrial areas, underground or in ducts.

Construction
1. Stranded copper conductor.
2. Inner semi-conductive layer.
3. XLPE insulation.
4. Outer semi-conductive layer.
5. Semi-conductive tape.
6. Copper tape screen.
7. Filler.
8. PVC outer jacket.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght
DC Conductor Resistance at 20 ° C
Operation Inductance (approx)
Operation Capacitance (approx)
Current Carrying Capacity
in ground at 20 ° C
in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

mH/km

μ F/km
A
A

3x25/16

39.5

2250

1000

0.7270

0.370

0.208

149

141

3x35/16

42.0

2700

1000

0.5240

0.352

0.229

176

171

3x50/16

45.0

3350

1000

0.3870

0.336

0.255

208

196

3x70/16

48.5

4150

1000

0.2680

0.318

0.288

255

249

3x95/16

53.0

5200

500

0.1930

0.303

0.324

307

307

3x120/16

57.0

6250

500

0.1530

0.292

0.359

353

353

3x150/25

60.5

7350

500

0.1240

0.284

0.388

396

406

3x185/25

64.5

8650

500

0.0991

0.276

0.424

447

464

3x240/25

71.0

10850

250

0.0754

0.267

0.469

523

548

3x300/25

77.5

13200

250

0.0601

0.263

0.486

581

632

3x400/35

86.0

16900

250

0.0470

0.257

0.521

653

726