Cables | Energy cables | Intermediate voltage cables

XLPE Insulated, Three Core Cables With Copper Conductor

1

18/30 kV or 19/33 kV

 
 
1

Code
YXC8V-R, N2XSEY, CU/XLPE/CTS/PVC
R:Stranded conductor

Standards
TS IEC 60502, BS 6622, VDE 0276

Technical Data
Max. operating temperature : 90 ° C
Max. short circuit temperature: 250 ° C (max. 5 sec.)
Rated voltage : 18/30 kV-19/33 kV
Min. bending radius : 15 x D
D : Cable outer diameter

Application
These are cables with low dielectric losses used in energy networks with sudden load changes. Laid in residential or industrial areas, underground or in ducts.

Construction
1. Stranded copper conductor.
2. Inner semi-conductive layer.
3. XLPE insulation.
4. Outer semi-conductive layer.
5. Semi-conductivee tape.
6. Copper tape screen.
7. Filler.
8. PVC outer jacket.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght
DC Conductor Resistance at 20 ° C
Operation Inductance (approx)
Operation Capacitance (approx)
Current Carrying Capacity
in ground at 20 ° C
in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

mH/km

μ F/km
A
A

3x35/16

68.0

5650

500

0.5240

0.457

0.114

-

-

3x50/16

71.5

6500

500

0.3870

0.434

0.124

214

217

3x70/16

75.0

7500

500

0.2680

0.410

0.137

261

269

3x95/16

79.0

8700

500

0.1930

0.389

0.150

313

326

3x120/16

83.0

9900

500

0.1530

0.372

0.163

356

377

3x150/25

86.0

11150

250

0.1240

0.360

0.174

400

426

3x185/25

90.0

12650

250

0.0991

0.348

0.188

441

488

3x240/25

97.0

15200

250

0.0754

0.331

0.209

510

576

3x300/25

102.0

17650

250

0.0601

0.321

0.226

604

651

3x400/35

110.0

21550

200

0.0470

0.307

0.251

-

-