Cables | Energy cables | Intermediate voltage cables

XLPE Insulated Double Steel Tape Armoured, Three Core Cables With Copper Conductor

1

3.6/6 kV

 
 
1

Code
YXC8VZ4V-R, N2XSEYBY, CU/XLPE/CTS/PVC/5TA/PVC
R:Stranded conductor

Standards
TS IEC 60502, BS 6622, VDE 0276

Technical Data
Max. operating temperature : 90 ° C
Max. short circuit temperature: 250 ° C (max. 5 sec.)
Rated voltage : 3.6/6 kV
Min. bending radius : 15 x D
D : Cable outer diameter

Application
These are cables with low dielectric losses used in energy networks with sudden load changes where mechanical stresses expected. Laid in residential or industrial areas, underground or in ducts.

Construction
1. Stranded copper conductor.
2. Inner semi-conductive layer.
3. XLPE insulation.
4. Outer semi-conductive layer.
5. Semi-conductivee tape.
6. Copper tape screen.
7. Filler.
8. PVC inner jacket.
9. Galvanized double steel tape.
10. PVC outer jacket.

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght
DC Conductor Resistance at 20 ° C
Operation Inductance (approx)
Operation Capacitance (approx)
Current Carrying Capacity
in ground at 20 ° C
in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

mH/km

μ F/km
A
A

3x25/16

44.5

3000

1000

0.7270

0.370

0.208

149

141

3x35/16

47.0

3500

1000

0.5240

0.352

0.229

176

171

3x50/16

50.0

4250

1000

0.3870

0.336

0.255

208

196

3x70/16

54.0

5150

500

0.2680

0.318

0.288

255

249

3x95/16

58.0

6200

500

0.1930

0.303

0.324

307

307

3x120/16

62.5

7350

500

0.1530

0.292

0.359

353

353

3x150/25

66.0

8600

500

0.1240

0.284

0.388

396

406

3x185/25

70.0

10000

250

0.0991

0.276

0.424

447

464

3x240/25

77.0

12350

250

0.0754

0.267

0.469

523

548

3x300/25

83.5

14900

250

0.0601

0.263

0.486

581

632

3x400/35

94.0

19550

250

0.0470

0.257

0.521

653

726