Cables | Energy cables | Intermediate voltage cables

XLPE Insulated Double Steel Tape Armoured, Three Core Cables With Copper Conductor

1

5.8/10 kV or 6.35/11 kV

 
 
1

Code
YXC8VZ4V-R, N2XSEYBY, CU/XLPE/CTS/PVC/STA/PVC
R:Stranded conductor

Standards
TS IEC 60502, BS 6622, VDE 0276

Technical Data
Max. operating temperature : 90 ° C
Max. short circuit temperature: 250 ° C (max. 5 sec.)
Rated voltage : 5.8/10 kV-6.35/11 kV
Min. bending radius : 15 x D
D : Cable outer diameter

Application
These are cables with low dielectric losses used in energy networks with sudden load changes where mechanical stresses expected. Laid in residential or industrial areas, underground or in ducts.

Construction
1. Stranded copper conductor.
2. Inner semi-conductive layer.
3. XLPE insulation
4. Outer semi-conductive layer
5. Semi-conductive tape
6. Copper tape screen
7. Filler.
8. PVC inner jacket.
9. Galvanized double steel tape.
10. PVC outer jacket

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght
DC Conductor Resistance at 20 ° C
Operation Inductance (approx)
Operation Capacitance (approx)
Current Carrying Capacity
in ground at 20 ° C
in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

mH/km

μ F/km
A
A

3x25/16

50.0

.3500

1000

0.7270

0.392

0.173

148

143

3x35/16

51.5

3950

1000

0.5240

0.374

0.189

178

173

3x50/16

54.5

4650

1000

0.3870

0.355

0.209

210

206

3x70/16

58.5

5600

500

0.2680

0.336

0.236

256

257

3x95/16

63.0

6800

500

0.1930

0.320

0.263

307

313

3x120/16

67.0

7900

500

0.1530

0.308

0.291

349

360

3x150/25

70.0

9100

500

0.1240

0.299

0.314

392

410

3x185/25
74.5
10550
250
0.0991
0.290

0.341

443

469

3x240/25

81.5

13000

250

0.0754

0.278

0.387

513

553

3x300/25

88.0

15900

250

0.0601

0.270

0.422

576

635

3x400/35

96.0

19800

250

0.0470

0.261

0.475

650

731