Cables | Energy cables | Intermediate voltage cables

XLPE insulated. Radial and Longitudinally Sealed, Single Core Cables With Copper Conductor

1

89/154 kV

 
 
1

Code
2XS(FL)2Y, CU/XLPE/LW/CWS/LW/PE

Standards
VDE 0276-632 - IEC 60840 TEST STANDARTS

Technical Data
Max. operating temperature : 90 ° C
Max. short circuit temperature: 250 ° C (max. 5 sec.)
Rated voltage : 89/154 kV
Min. bending radius : 15 x D
D : Cable outer diameter

Application
These are cables with low dielectric losses used in energy networks with sudden load changes. Laid in residential or industrial areas, underground or in ducts. If the cable gets water inside due to the mechanical demages, swellable tapes prevent the movement of the water inside the cable.

Construction
1. Stranded copper conductor.
2. Inner semi-conductive layer.
3. XLPE insulation
4. Outer semi-conductive layer
5. Semi-conductive swelible tape
6. Copper tape screen
7. Swelible tape.
8. Aluminium tape
9. PVC outer jacket

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght
DC Conductor Resistance at 20 ° C
Operation Inductance (approx)
Operation Capacitance (approx)
Current Carrying Capacity
in ground at 20 ° C
in air at 30 ° C

mm 2

mm

kg/km

m

ohm/km

mH/km

μ F/km
A
A

3x35/16

62.0

5350

500

0.5240

0.416

0.141

183

182

3x50/16

65.0

6100

500

0.3870

0.395

0.155

216

217

3x70/16

69.0

7100

500

0.2680

0.373

0.172

264

269

3x95/16

73.0

8300

500

0.1930

0.355

0.191

316

326

3x120/16

77.0

9500

500

0.1530

0.340

0.209

360

377

3x150/25

81.0

10900

250

0.1240

0.329

0.225

404

426

3x185/25

86.0

13000

250

0.0991

0.319

0.243

457

488

3x240/25

92.5

15550

250

0.0754

0.304

0.273

532

576

3x300/25

98.0

18000

250

0.0601

0.295

0.296

599

654

3x400/35

106.5

22200

200

0.0470

0.284

0.331

685

750