Cables | Energy cables | High voltage cables

XLPE insulated. Radial and Longitudinally Sealed, Single Core Cables With Copper Conductor

1

40/69 kV

 
 

Code
2XS(FL)2Y, CU/XLPE/LW/CWS/LW/PE

Standards
VDE 0276-632 - IEC 60840 TEST STANDARTS

Technical Data
Max. operating temperature : 90 ° C
Max. short circuit temperature: 250 ° C (max. 5 sec.)
Rated voltage : 89/154 kV
Min. bending radius : 20 x D
D : Cable outer diameter

Application
These are cables with low dielectric losses used in energy networks with sudden load changes. Laid in residential or industrial areas, underground or in ducts. If the cable gets water inside due to the mechanical demages, swellable tapes prevent the movement of the water inside the cable.

Construction
1. Stranded copper conductor.
2. Inner semi-conductive layer.
3. XLPE insulation
4. Outer semi-conductive layer
5. Semi-conductive swelible tape
6. Copper tape screen
7. Swelible tape.
8. Aluminium tape
9. PVC outer jacket

Dimensiuni si greutati

Proprietati electrice

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght
DC Conductor Resistance at 20 ° C
Current Carrying Capacity
in ground at 20 ° C
pipe duct at 20 ° C
in air (30 ° C)

mm 2

mm

kg/km

m

ohm/km

A

A

1x240

61.0

4700

0.0754

0.18

530

483

692

606

1x300

63.0

5400

0.0601

0.19

599

544

795

693

1x400

66.0

6300

0.0470

0.21

683

616

925

802

1x500

70.0

7600

0.0366

0.23

780

729

1075

929

1x630

75.0

9000

0.0283

0.26

886

828

1247

1066

1x800

79.0

10700

0.0221

0.28

997

929

1432

1210

1x1000

84.0

12900

0.0176

0.31

1173

1087

1728

1473

1x1200

90.0

15000

0.0151

0.33

1270

1173

1894

1611

1x1600

95.0

18800

0.0113

0.37

1465

1375

2245

1883

1x2000

102.0

22800

0.0090

0.41

1627

1530

2556

2111