Cables | Energy cables | High voltage cables

XLPE insulated. Radial and Longitudinally Sealed, Single Core Cables With Copper Conductor

1

64/110 kV

 
 

Code
2XS(FL)2Y, CU/XLPE/LW/CWS/LW/PE

Standards
VDE 0276-632 - IEC 60840 TEST STANDARTS

Technical Data
Max. operating temperature : 90 ° C
Max. short circuit temperature: 250 ° C (max. 5 sec.)
Rated voltage : 89/154 kV
Min. bending radius : 20 x D
D : Cable outer diameter

Application
These are cables with low dielectric losses used in energy networks with sudden load changes. Laid in residential or industrial areas, underground or in ducts. If the cable gets water inside due to the mechanical demages, swellable tapes prevent the movement of the water inside the cable.

Construction
1. Stranded copper conductor.
2. Inner semi-conductive layer.
3. XLPE insulation
4. Outer semi-conductive layer
5. Semi-conductive swelible tape
6. Copper tape screen
7. Swelible tape.
8. Aluminium tape
9. PVC outer jacket

Dimensiuni si greutati

Proprietati electrice

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght
DC Conductor Resistance at 20 ° C
Current Carrying Capacity
in ground at 20 ° C
pipe duct at 20 ° C
in air (30 ° C)

mm 2

mm

kg/km

m

ohm/km

A

A

1x240

68.0

5400

0.0754

0.18

528

495

682

605

1x300

71.0

6100

0.0601

0.19

597

559

783

692

1x400

74.0

7100

0.0470

0.21

681

650

909

800

1x500

78.0

8400

0.0366

0.22

775

739

1053

922

1x630

82.0

9900

0.0283

0.24

884

841

1226

1065

1x800

86.0

11600

0.0221

0.26

994

945

1406

1208

1x1000

92.0

14000

0.0176

0.29

1169

1106

1695

1465

1x1200

97.0

16000

0.0151

0.31

1264

1231

1849

1595

1x1600

104.0

20000

0.0113

0.34

1456

1415

2185

1860

1x2000

115.0

24000

0.0090

0.37

1618

1570

2487

2089