Cables | Energy cables | High voltage cables

XLPE insulated. Radial and Longitudinally Sealed, Single Core Cables With Copper Conductor

1

89/154 kV

 
 
1

Code
2XS(FL)2Y, CU/XLPE/LW/CWS/LW/PE

Standards
VDE 0276-632 - IEC 60840 TEST STANDARTS

Technical Data
Max. operating temperature : 90 ° C
Max. short circuit temperature: 250 ° C (max. 5 sec.)
Rated voltage : 89/154 kV
Min. bending radius : 20 x D
D : Cable outer diameter

Application
These are cables with low dielectric losses used in energy networks with sudden load changes. Laid in residential or industrial areas, underground or in ducts. If the cable gets water inside due to the mechanical demages, swellable tapes prevent the movement of the water inside the cable.

Construction
1. Stranded copper conductor.
2. Inner semi-conductive layer.
3. XLPE insulation
4. Outer semi-conductive layer
5. Semi-conductive swelible tape
6. Copper tape screen
7. Swelible tape.
8. Aluminium tape
9. PVC outer jacket

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght
DC Conductor Resistance at 20 ° C
Current Carrying Capacity
in ground at 20 ° C
pipe duct at 20 ° C
in air (30 ° C)

mm 2

mm

kg/km

m

ohm/km

A

A

1x300

85.0

8500

0.0601

0.22

591

553

765

684

1x400

89.0

9600

0.0470

0.24

673

629

887

789

1x500

93.0

10800

0.0366

0.26

766

713

1027

907

1x630

96.0

12400

0.0283

0.29

871

829

1193

1043

1x800

102.0

14200

0.0221

0.31

977

928

1367

1181

1x1000

106.0

16500

0.0176

0.34

1143

1081

1639

1415

1x1200

110.0

18500

0.0151

0.37

1232

1208

1790

1535

1x1600

118.0

22500

0.0113

0.41

1404

1382

2100

1765

1x2000

126.0

26500

0.0090

0.45

1554

1523

2384

1973