Cables | Energy cables | High voltage cables

XLPE Insulated, Lead Sheathed, Single Core Cables With Copper Conductor

1

64/110 kV

 
 
1

Code
2XK2Y, CU/XLPE/Lead/PE

Standards
VDE 276-632 - IEC 60840 TEST SANDARTS

Technical Data
Max. operating temperature : 90 ° C
Max. short circuit temperature: 250 ° C (max. 5 sec.)
Rated voltage : 64/110 kV
Min. bending radius : 20 x D
D : Cable outer diameter

Application
These are cables with low dielectric losses used in energy networks : with sudden load changes. Laid in residential or industrial areas, underground or in ducts.

Construction
1. Stranded copper conductor.
2. Inner semi-conductive layer.
3. XLPE insulation
4. Outer semi-conductive layer
5. Semi-conductive swelible tape
6. Lead sheath
7. PE outer jacket

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght
DC Conductor Resistance at 20 ° C
Current Carrying Capacity
in ground at 20 ° C
pipe duct at 20 ° C
in air (30 ° C)

mm 2

mm

kg/km

m

ohm/km

A

A

1x240

69.0

9800

0.0754

0.18

533

498

692

617

1x300

72.0

11100

0.0601

0.19

602

563

794

705

1x400

75.0

12500

0.0470

0.21

687

654

923

816

1x500

80.0

14000

0.0366

0.23

782

744

1068

939

1x630

84.0

16300

0.0283

0.26

891

846

1243

1083

1x800

88.0

18800

0.0221

0.28

1001

949

1425

1229

1x1000

95.0

22300

0.0176

0.31

1176

1108

1718

1486

1x1200

100.0

25100

0.0151

0.33

1269

1235

1871

1612

1x1600

107.0

30500

0.0113

0.37

1455

1415

2206

1870

1x2000

115.0

36100

0.0090

0.41

1609

1562

2505

2087