Cables | Energy cables | High voltage cables

XLPE Insulated, Lead Sheathed, Single Core Cables With Copper Conductor

1

89/154 kV

 
 
1

Code
2XK2Y, CU/XLPE/Lead/PE

Standards
VDE 276-632 - IEC 60840 TEST SANDARTS

Technical Data
Max. operating temperature : 90 ° C
Max. short circuit temperature: 250 ° C (max. 5 sec.)
Rated voltage : 89/154 kV
Min. bending radius : 20 x D
D : Cable outer diameter

Application
These are cables with low dielectric losses used in energy networks with sudden load changes. Laid in residential or industrial areas, underground or in ducts.

Construction
1. Stranded copper conductor.
2. Inner semi-conductive layer.
3. XLPE insulation
4. Outer semi-conductive layer
5. Semi-conductive swelible tape
6. Lead sheath
7. PE outer jacket

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght
DC Conductor Resistance at 20 ° C
Current Carrying Capacity
in ground at 20 ° C
pipe duct at 20 ° C
in air (30 ° C)

mm 2

mm

kg/km

m

ohm/km

A

A

1x300

82.0

12600

0.0601

0.19

598

557

775

698

1x400

85.0
14200
0.0470
0.21
682
648

898

805

1x500

88.0

16000

0.0366

0.23

777

736

1042

928

1x630
93.0
18300
0.0283
0.26
886
836
1214
1073

1x800

97.0
20900
0.0221
0.28

996

939

1391

1218
1x1000
104.0
24300
0.0176
0.31
1168
1131
1670
1464

1x1200

107.0
27200
0.0151
0.33
1259

1221

1825

1589

1x1600

115.0
32700
0.0113

0.37

1445

1398
2152
1845

1x2000

121.0

38500

0.0090

0.41

1597

1541

2445

2060