Pair no : 1 - 20
Cross Section : 0.80 mm
Cables | Halogen Free Flame Redundant cables

JE-H(St)H FE180/E30  HFFR FIRE ALARM CABLE

Application

Safety cables are used in all locations where a speacial protection against, fire and fire damage is necessary such as industrial plants, schools, hospitals, shopping centers, airports, hotels where human life and material assets are to be protected. These halogen-free cables are used for telecomunications and information processing systems, transmission of analog and digital signals. These cables maintaining function are used in applications with high safety requirements and where a certain functional maintenance must be assured in the event of fire. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. No corrosive gases are emitted in the event of fire. The use of installation cables for power cable applications and underground installation is not permitted.

Cable design Tehnical data
Conductor : Plain Cu conductor,solid.
Insulation : Halogen free elastomer Compus.
Core idenfication : VDE 0815
Pair : Two conductors twisted to a pair
Lay-up : Pairs laid up in layers of optimum pitch
Separator : Polyester tape
Wrapping : Fiber glass textile tape
Outer Sheath : HFFR compound
Screen : With drain wire under the AL-PES tape
Sheath Colour : Orange
Standard : VDE 0815
Insulation resistance : > 100 Mohm.km
Mutual Capacitance (800 Hz) : 120 nF/km
Operating voltage : 300 V
Test voltage (AC 50 Hz) : 1200 V
Temperature range : -30 °C / +70 °C
Min. Bending radius : 15 x Cable diameter
Flame test : IEC 332-1 & IEC 332-3
Insulation inteGreyty : IEC 331, TS 3164