Pair: 2 - 25
Cross-Section: 0,22 mm2 - 2,5 mm2
Cables | Halogen Free Flame Redundant cables

LIH(St)H-PF  HFFR SIGNAL AND CONTROL CABLE

Application

These twisted pair and screened data transmision cables are used for data engineering where low current consumptions are required and transmision of the data must be continuous where the connection of computers, information and transmission systems. And also screen provides protection against external pulses. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. No corrosive gases are emitted in the event of fire.

Cable design Tehnical data
Conductor : Plain Cu wires, flexible, IEC 228-5.
Insulation : HFFR compound
Core identification : DIN 47100 or numbered cores.
Pair : Two conductors twisted to a pair
Lay-up : Pairs laid up in layers of optimum pitch
Separator : Poliester
Screen : With drain under the AL-PES bant.
Outer Sheath : HFFR compound
Sheath Colour : RAL 7001, Grey
Standard : VDE 0812, VDE 0815
Insulation resistance : > 100 Mohm.km
Mutual Capacitance(800 Hz) : 120 nF/km
Operating voltage : 300 V
Test voltage (AC 50 Hz) : 1200 V
Temperature range : -30 °C / +70 °C
Min. Bending radius : 15 x Cable diameter
Flame test : IEC 332-1 & IEC 332-3