Pair: 2 - 25
Cross-Section: 0,22 mm2 - 2,5 mm2
Cables | Halogen Free Flame Redundant cables

LIH(St)H  HFFR Signal and Control Cable

Application

These control and connecting cables are used in instrumentation and control engineering; in industrial electronics, computers, information and transmission systems office machines; data transmission cables for voice frequncy transmission. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. No corrosive gases are emitted in the event of fire.

Cable design Tehnical data
Conductor : Plain Cu wires, flexible, IEC 228-5.
Insulation : HFFR compound
Core identification : DIN 47100 sau miezuri numerotate
Lay-up : Pairs laid up in layers of optimum pitch.
Separator : Poliester
Screen : With drain under the AL-PES bant.
Outer Sheath : HFFR compound
Sheath Colour : RAL 7001, Grey
Standard : VDE 0812, VDE 0815
Insulation resistance : > 100 Mohm.km
Mutual Capacitance(800 Hz) : 120 nF/km
Operating voltage : 300 V
Test voltage (AC 50 Hz) : 1200 V
Temperature range : -30 °C / +70 °C
Min. Bending radius : 15 x Cable diameter
Flame test : IEC 332-1 & IEC 332-3