Core: 2 - 25
Cross-section: 0.22 mm? - 2.5 mm?
Cables | Halogen Free Flame Redundant cables

LIHCH  HFFR Signal and Control Cable

Application

These screened non-halogen control and connecting cables are used in instrumentation and control engineering where low current consumptionsare required and transmission of the data must be continuous , for example in industrial electronics, information and transmission systems office machines. And also consisting of tinned copper wires as screen provides protection against external pulses. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. No corrosive gases are emitted in the event of fire.

Cable design Tehnical data
Conductor : Plain Cu wires, flexible ,IEC 228-5
Insulation : HFFR kompound
Core identification : DIN 47100 or numbered core.
Lay-up : Cores laid up in layers of optimum pitch
Separator : Poliester
Screen : Braid of tinned Cu wires, %85 coverage
Outer Sheath : HFFR compound
Sheath Colour : RAL 7001, Grey
It has a flame test certification
Standard : VDE 0812, VDE 0815
Insulation resistance : > 100 Mohm.km
Mutual Capacitance (800 Hz) : 120 nF/km
Operating voltage : 300 V
Test voltage : 1200 V
Temperature range : -30 °C / +70 °C
Min. Bending radius : 15 x Cable diameter
Flame test : IEC 332-1 & IEC 332-3