Pair:2 - 5
Cross-Section: 1,50 mm2 - 6 mm2
Cables | Halogen Free Flame Redundant cables

N2XH FE 180  HFFR FIRE SECURITY CABLE

Application

Safety cables are used in all locations where a speacial protection against, fire and fire damage is necessary such as industrial plants, schools, hospitals, shopping centers, airports, hotels where human life and material assets are to be protected and where large emergency running times are necessary. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. No corrosive gases are emitted in the event of fire. These cables can work according to IEC 331 insulation inteGreyty for minimum 180 minutes. They are installed as energy, power cables. They may not be installed directly into the ground and into the water.

Cable design Tehnical data
Conductor : Plain Cu wire, IEC 228-1.
Insulation : Double layer ,mica tape and XL polymer or fire resistant halogen-free elastomer comp.
Core identification : VDE 0293-308
Lay-up : Cores laid up in layers of optimum pitch
Filler : HFFR filler compound
Outer Sheath : HHFR compound.
Sheath Colour : Orange
Standard : VDE 0276-604
Conductor operating temp. : 90 °C
Rated voltage : 0,6 / 1 kV.
Test voltage (AC 50 Hz) : 3,5 kV.
Temperature range : -30 °C / +90 °C
Min. Bending radius : 15 x Cable diameter
Flame test : IEC 332-1 & IEC 332-3
Insulation inteGreyty (FE 180) IEC 331, TS 3164