Pair:2 - 25
Cross-Section: 0,75 mm2 - 2,5 mm2
Cables | Halogen Free Flame Redundant cables

NHSLHCH-JZ  HFRR CONTROL CABLE

Application

Safety cables are used in all locations as a control cables where a speacial protection against, fire and fire damage is necessary such as industrial plants, schools, hospitals, shopping centers, airports, hotels where human life and material assets are to be protected. The screen above the inner sheat protects against external interference pulses and ensures an interference-free transmission. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. No corrosive gases are emitted in the event of fire. These cables are installed as energy ,power cables. They may not be installed directly into the ground and into the water.

Cable design Tehnical data
Conductor : Plain Cu wire, IEC 228-5
Insulation : HHFR compound.
Core identification : According to VDE 0293 white imprinting numbers
on black cores, with green-yellow.
Lay-up : Cores laid up in layers of optimum pitch
Inner Sheath : HFFR filler compound.
Screen : Braid of tinned Cu wires, %85 coverage.
Outer Sheath : HHFR compound.
Sheath Colour : RAL 7001, Grey
Standard : According VDE 0250 -405
Insulation resistance : > 20 Mohm.km
Rated Voltage Uo/U : 300 / 500 V.
Test voltage (AC 50 Hz) : 2000 V
Temperature range : -30 °C / +70 °C
Min. Bending radius : 15 x Cable diameter
Flame test : IEC 332-1 & IEC 332-3