Cables | Halogen Free Flame Redundant cables

NHXH FE 180 / E30  HFFR FIRE SECURITY CABLE

Application

: Safety cables are used in all locations where a speacial protection against, fire and fire damage is necessary such as industrial plants, schools, hospitals, shopping centers, airports, hotels where human life and material assets are to be protected and where large emergency running times are necessary. In case of fire, these cables inhibit the propagation of the flames whereby the development of smoke is extremely low. No corrosive gases are emitted in the event of fire. These cables can work according to IEC 331 insulation inteGreyty for minimum 180 minutes. They are installed as energy, power cables. They may not be installed directly into the ground and into the water.

Cable design Tehnical data
Conductor : Plain Cu wire, IEC 228-1 or 2.
Insulation : Cross-linked elastomer Compus.
Core identification : VDE 0293-308
Lay-up : Cores laid up in layers of optimum pitch
Filler : HFFR filler compound
Outer Sheath : HHFR Compus
Sheath Colour : Orange
Standard : According to VDE 0266
Conductor operating temp. : 90 °C
Rated voltage Uo/U : 0,6 / 1 kV
Test voltage (AC 50 Hz) : 3,5 kV.
Temperature range : -30 °C / +90 °C
Min. Bending radius : 15 x Cable diameter
Flame test : IEC 332-1 & IEC 332-3
Insulation inteGreyty (FE 180) IEC 331,TS 3164