Cables | Electrical installation cables | |
PVC Insulated, Non-Sheadted Single Core Cable With Copper Conductor |
|
1 | |
Code Standards Max.operating temperature : 70 ° C Short circuit temperature : 160 ° C (max. 5 sec.) Rated voltage : 300/500 V, 450/750 V Application In dry rooms, switch and distribution boards, for laying in conduit on and under plaster and on insulating supports above plaster. Construction 1. Solid or stranded copper conductor. 2. PVC insulation. |
DIMENSIONS AND WEIGHTS |
ELECTRICAL PROPERTIES |
|||||
Nominal |
Overall Diameter (approx.) |
Net Weight (approx.) |
Delivery Lenght |
DC Conductor Resistance at 20 ° C |
Current carrying capacity
|
|
In ground at 20 ° C |
In Air at 30 ° C |
|||||
mm 2 |
mm |
kg/km |
m |
ohm/km |
A |
A |
0.5re * |
2.1 |
8 |
100 |
36.0 |
- |
9 |
0.75re * |
2.3 |
11 |
100 |
24.5 |
- |
15 |
1 .0 re * |
2.5 |
14 |
100 |
18.1 |
11 |
19 |
1.5re |
2.8 |
20 |
100 |
12.1 |
15 |
24 |
2.5re |
3.3 |
31 |
100 |
7.41 |
20 |
32 |
4re |
3.8 |
46 |
100 |
4.61 |
25 |
42 |
6re |
4.3 |
54 |
100 |
3.08 |
33 |
54 |
1Ore |
5.6 |
108 |
100 |
1.83 |
45 |
73 |
10rm |
6.0 |
111 |
100 |
1.83 |
45 |
73 |
16rm |
7.0 |
170 |
1000 |
1.15 |
61 |
98 |
25rm |
8.5 |
260 |
1000 |
0.727 |
83 |
129 |
35rm |
9.5 |
355 |
1000 |
0.524 |
103 |
158 |
50rm |
11.0 |
505 |
1000 |
0.387 |
132 |
198 |
70rm |
13.0 |
694 |
1000 |
0.268 |
165 |
245 |
95rm |
15.0 |
938 |
1000 |
0.193 |
197 |
292 |
120rm |
16.5 |
1172 |
1000 |
0.153 |
235 |
344 |
150rm |
18.0 |
1465 |
1000 |
0.124 |
- |
391 |
185rm |
20.0 |
1808 |
1000 |
0.0991 |
- |
448 |
240rm |
23.0 |
2343 |
1000 |
0.0754 |
- |
528 |
300rm |
26.0 |
2921 |
1000 |
0.0601 |
- |
608 |
400rm |
29.5 |
3875 |
1000 |
0.0470 |
- |
726 |