| Cables | Energy cables | Low voltage cables | |
PVC Insulated, Multi-Core Cables With Copper Conductor | 
  |
| 1 | |
0.6/1 kV | 
  |
![]()  | 
    ![]()  | 
  
Code  Standards Max. operating temperature : 70 ° C Max. short circuit temperature : (max. 5 sec.) Cross section < 300 mm : 160 ° C Cross section > 300 mm : 140 ° C Rated voltage : 0.6/1 kV Min. bending radius : 12 x D D : Cable outer diameter  Application 1. Solid or stranded copper conductor. 2. PVC insulation. 3. Filler. 4. PVC outer sheath.  | 
  |
DIMENSIONS AND WEIGHTS  | 
    ELECTRICAL PROPERTIES  | 
  |||||
 Nominal   | 
    Overall Diameter (approx.)  | 
    Net Weight (approx.)  | 
    Delivery Lenght  | 
    DC Conductor Resistance at 20 ° C  | 
    Capacity in ground at 30 ° C  | 
    Capacity in air at 30 ° C  | 
  
mm 2  | 
    mm  | 
    kg/km  | 
    m  | 
    ohm/km  | 
    A  | 
    A  | 
  
3x16+10  | 
    21.5  | 
    970  | 
    1000  | 
    1.1500  | 
    98  | 
    80  | 
  
3x25+16  | 
    25.0  | 
    1400  | 
    1000  | 
    0.7270  | 
    128  | 
    106  | 
  
3x35+16  | 
    27.0  | 
    1750  | 
    1000  | 
    0.5240  | 
    157  | 
    131  | 
  
3x50+25  | 
    31.0  | 
    2400  | 
    1000  | 
    0.3870  | 
    185  | 
    159  | 
  
3x70+35  | 
    35.0  | 
    3300  | 
    1000  | 
    0.2680  | 
    228  | 
    202  | 
  
3x95+50  | 
    40.0  | 
    4400  | 
    1000  | 
    0.1930  | 
    275  | 
    244  | 
  
3x120+70  | 
    44.5  | 
    5550  | 
    500  | 
    0.1530  | 
    313  | 
    282  | 
  
3x150+70  | 
    48.0  | 
    6550  | 
    500  | 
    0.1240  | 
    353  | 
    324  | 
  
3x185+95  | 
    53.0  | 
    8200  | 
    500  | 
    0.0991  | 
    399  | 
    371  | 
  
3x240+120  | 
    60.5  | 
    10600  | 
    500  | 
    0.0754  | 
    464  | 
    436  | 
  
3x300+150  | 
    68.0  | 
    13100  | 
    250  | 
    0.0601  | 
    524  | 
    481  | 
  
3x400+185  | 
    76.0  | 
    17000  | 
    250  | 
    0.0470  | 
    600  | 
    560  |