Cables | Energy cables | Low voltage cables | |
PVC Insulated, Control Cables With Copper Conductor |
|
1 | |
0.6/1 kV |
|
![]() |
![]() |
Code Standards Max. operating temperature : 70°C Max. short circuit temperature : (max. 5 sec.) Rated voltage : 0.6/1 kV Min. bending radius : 12 x D D : Cable outer diameter Application 1. Solid or stranded copper conductor. 2.PVC insulation. 3.Filler. 4. PVC outer sheath. |
DIMENSIONS AND WEIGHTS |
ELECTRICAL PROPERTIES |
|||||
Nominal |
Overall Diameter (approx.) |
Net Weight (approx.) |
Delivery Lenght |
DC Conductor Resistance at 20 ° C |
Current carrying capacity |
|
in ground at 20 ° C | in air at 30 ° C | |||||
mm 2 |
mm |
kg/km |
m |
ohm/km |
A |
A |
5x2,5 |
14.5 |
350 |
1000 |
7.410 |
23.8 |
18.8 |
6x2,5 |
15.5 |
410 |
1000 |
7.410 |
22.1 |
17.5 |
7x2,5 |
16.0 |
415 |
1000 |
7.410 |
20.4 |
16.3 |
8x2,5 |
17.0 |
500 |
1000 |
7.410 |
18.7 |
15.0 |
10x2,5 |
19.0 |
595 |
1000 |
7.410 |
17.0 |
13.8 |
12x2,5 |
19.5 |
650 |
1000 |
7.410 |
16.2 |
13.1 |
14x2,5 |
20.5 |
730 |
1000 |
7.410 |
15.3 |
12.5 |
16x2,5 |
21.5 |
825 |
1000 |
7.410 |
14.5 |
11.9 |
19x2,5 |
22.5 |
920 |
1000 |
7.410 |
13.6 |
11.3 |
21x2,5 |
23.5 |
1010 |
1000 |
7.410 |
12.9 |
10.8 |
24x2,5 |
26.0 |
1190 |
1000 |
7.410 |
11.9 |
10.0 |
27x2,5 |
26.5 |
1280 |
1000 |
7.410 |
11.6 |
9.7 |
30x2,5 |
27.0 |
1380 |
1000 |
7.410 |
11.2 |
9.4 |
37x2,5 |
29.5 |
1660 |
1000 |
7.410 |
10.6 |
9.1 |
40x2,5 |
30.5 |
1800 |
1000 |
7.410 |
10.2 |
8.8 |
48x2,5 |
34.0 |
2135 |
1000 |
7.410 |
9.5 |
8.3 |
52x2,5 |
34.5 |
2320 |
1000 |
7.410 |
8.9 |
7.8 |
61x2,5 |
37.0 |
2630 |
1000 |
7.410 |
8.5 |
7.5 |