Cables | Energy cables | Low voltage cables | |
PVC Insulated, Flat Steel Wire Armoured, Multi-Core Cables With Copper Conductor |
|
1 | |
0.6/1 kV |
|
![]() |
![]() |
Code Standards Max. operating temperature : 70"C Max. short circuit temperature : (max. 5 sec.) Cross section < 300 mm : 160°C Cross section > 300 mm : 140°C Rated voltage : 0.6/1 kV Min. bending radius : 12 x D D : Cable outer diameter Application 1. Stranded copper conductor. 2. PVC insulation. 3. Filler. 4. Galvanized flat steel wire. 5. Galvanized steel binding tape. 6. PVC outer sheath. |
DIMENSIONS AND WEIGHTS |
ELECTRICAL PROPERTIES |
|||||
Nominal |
Overall Diameter (approx.) |
Net Weight (approx.) |
Delivery Lenght |
DC Conductor Resistance at 20 ° C |
Curent carrying capacity |
|
in ground at 20 ° C | in air at 30 ° C | |||||
mm 2 |
mm |
kg/km |
m |
ohm/km |
A |
A |
3x16 |
23.0 |
1250 |
1000 |
1.15 |
98 |
80 |
3x25 |
26.0 |
1700 |
1000 |
0.727 |
128 |
106 |
3x35 |
28.0 |
2100 |
1000 |
0.524 |
157 |
131 |
3x50 |
32.0 |
2750 |
1000 |
0.387 |
185 |
159 |
3x70 |
36.0 |
3600 |
1000 |
0.268 |
228 |
202 |
3x95 |
41.0 |
4700 |
1000 |
0.193 |
275 |
244 |
3x120 |
44.5 |
5650 |
500 |
0.153 |
313 |
282 |
3x150 |
49.0 |
6900 |
500 |
0.124 |
353 |
324 |
3x185 |
54.0 |
8350 |
500 |
0.0991 |
399 |
371 |
3x240 |
61.0 |
10700 |
250 |
0.0754 |
464 |
436 |
3x300 |
69.0 |
13200 |
250 |
0.0601 |
524 |
481 |
3x400 |
77.0 |
17150 |
250 |
0.0470 |
600 |
560 |