| Cables | Energy cables | Low voltage cables | |
PVC Insulated, Multi-Core Cables With Aluminium Conductor | 
  |
| 1 | |
0.6/1 kV | 
  |
![]()  | 
    ![]()  | 
  
Code  Standards Max. operating temperature : 70°C Max. short circuit temperature : (max. 5 sec.) Cross section < 300 mm : 160°C Cross section > 300 mm : 140°C Rated voltage : 0.6/1 kV Min. bending radius : 12 x D D : Cable outer diameter  Application  Construction
  | 
  |
DIMENSIONS AND WEIGHTS  | 
    ELECTRICAL PROPERTIES  | 
  |||||
 Nominal   | 
    Overall Diameter (approx.)  | 
    Net Weight (approx.)  | 
    Delivery Lenght 
     | 
    DC Conductor Resistance at 20 ° C  | 
    Current carrying capacity         | 
  |
in ground at 20 ° C  | 
    in air at 30 ° C  | 
  |||||
mm 2  | 
    mm  | 
    kg/km  | 
    m  | 
    ohm/km  | 
    A  | 
    A  | 
  
3x25+16  | 
    25.0  | 
    850  | 
    1000  | 
    1.2000  | 
    99  | 
    83  | 
  
3x35+16  | 
    27.0  | 
    1000  | 
    1000  | 
    0.8680  | 
    118  | 
    102  | 
  
3x50+25  | 
    32.0  | 
    1350  | 
    1000  | 
    0.6410  | 
    142  | 
    124  | 
  
3x70+35  | 
    36.0  | 
    1800  | 
    1000  | 
    0.4430  | 
    176  | 
    158  | 
  
3x95+50  | 
    41.0  | 
    2350  | 
    1000  | 
    0.3200  | 
    211  | 
    190  | 
  
3x120+70  | 
    45.5  | 
    2900  | 
    1000  | 
    0.2530  | 
    242  | 
    221  | 
  
3x150+70  | 
    49.5  | 
    3450  | 
    1000  | 
    0.2060  | 
    270  | 
    252  | 
  
3x185+95  | 
    55.0  | 
    4250  | 
    500  | 
    0.1640  | 
    308  | 
    289  | 
  
3x240+120  | 
    61.5  | 
    5350  | 
    500  | 
    0.1250  | 
    363  | 
    339  | 
  
3x300+150  | 
    68.0  | 
    6550  | 
    500  | 
    0.1000  | 
    412  | 
    377  | 
  
3x400+185  | 
    76.5  | 
    8400  | 
    500  | 
    0.0778  | 
    475  | 
    444  |