Cables | Energy cables | High voltage cables | |
XLPE Insulated, Lead Sheathed, Single Core Cables With Copper Conductor |
|
1 | |
89/154 kV |
|
![]() |
![]() |
1 | |
Code Standards Technical Data These are cables with low dielectric losses used in energy networks with sudden load changes. Laid in residential or industrial areas, underground or in ducts. Construction
|
DIMENSIONS AND WEIGHTS |
ELECTRICAL PROPERTIES |
|||||||
Nominal |
Overall Diameter (approx.) |
Net Weight (approx.) |
Delivery Lenght
|
DC Conductor Resistance at 20 ° C |
Current Carrying Capacity |
|||
in ground at 20 ° C |
pipe duct at 20 ° C |
in air (30 ° C)
|
||||||
mm 2 |
mm |
kg/km |
m |
ohm/km |
A |
A
|
![]() |
![]() |
1x300 |
82.0 |
12600 |
0.0601 |
0.19 |
598 |
557 |
775 |
698 |
1x400 |
85.0 |
14200 |
0.0470 |
0.21 |
682 |
648 |
898 |
805 |
1x500 |
88.0 |
16000 |
0.0366 |
0.23 |
777 |
736 |
1042 |
928 |
1x630 |
93.0 |
18300 |
0.0283 |
0.26 |
886 |
836 |
1214 |
1073 |
1x800 |
97.0 |
20900 |
0.0221 |
0.28 |
996 |
939 |
1391 |
1218 |
1x1000 |
104.0 |
24300 |
0.0176 |
0.31 |
1168 |
1131 |
1670 |
1464 |
1x1200 |
107.0 |
27200 |
0.0151 |
0.33 |
1259 |
1221 |
1825 |
1589 |
1x1600 |
115.0 |
32700 |
0.0113 |
0.37 |
1445 |
1398 |
2152 |
1845 |
1x2000 |
121.0 |
38500 |
0.0090 |
0.41 |
1597 |
1541 |
2445 |
2060 |