Cables | Halogen Free Flame Redundant cables | |
Halogen Free, Flame Retardant, Single Core Cables With Copper Conductor. |
|
1 | |
300/500V |
|
1 | |
Code Standards Technical Data Used in energy networks in refineries, mines, hotels, schools, tunnels, high constructions, hospitals, power plant, data processing centers, business centers where there is a risk of fire. Construction
|
DIMENSIONS AND WEIGHTS |
ELECTRICAL PROPERTIES |
|||||
Nominal |
Overall Diameter (approx.) |
Net Weight (approx.) |
Delivery Lenght
|
DC Conductor Resistance at 20 ° C |
Current Carrying Capacity |
|
in ground (20 ° C) |
in air (30 ° C) |
|||||
mm 2 |
mm |
kg/km |
m |
ohm/km |
A |
A
|
* 0.5 re |
2.0 |
8 |
100 |
36.00 |
- |
- |
* 0.75 re |
2.2 |
11 |
100 |
24.50 |
- |
15 |
* 1.0 re |
2.4 |
14 |
100 |
18.10 |
11 |
19 |
** 1.5 re |
2.6 |
20 |
100 |
12.10 |
16 |
24 |
** 2.5 re |
3.2 |
32 |
100 |
7.41 |
20 |
32 |
** 4.0 re |
3.9 |
46 |
100 |
4.61 |
27 |
42 |
** 6.0 re |
4.4 |
65 |
100 |
3.08 |
35 |
54 |
**10 re |
5.6 |
108 |
100 |
1.83 |
48 |
73 |
10 re |
6.1 |
115 |
100 |
1.83 |
48 |
73 |
16 re |
6.8 |
170 |
100 |
1.15 |
65 |
98 |
25 rm |
8.8 |
260 |
1000 |
0.727 |
88 |
129 |
35 rm |
9.8 |
355 |
1000 |
0.524 |
110 |
158 |
50 rm |
11.5 |
500 |
1000 |
0.387 |
140 |
198 |
70 rm |
13.2 |
680 |
1000 |
0.268 |
175 |
245 |
95 rm |
15.0 |
930 |
1000 |
0.193 |
210 |
292 |
120 rm |
17.0 |
1170 |
1000 |
0.153 |
250 |
344 |
150 rm |
19.0 |
1450 |
1000 |
0.124 |
- |
391 |
185 rm |
21.0 |
1850 |
1000 |
0.0991 |
- |
448 |
240 rm |
24.5 |
2350 |
1000 |
0.0754 |
- |
528 |
300 rm |
27.0 |
2950 |
1000 |
0.0601 |
- |
645 |
400 rm |
31.0 |
3900 |
1000 |
0.0470 |
- |
770 |
* H05Z1-U
** H07Z1-U
re: Bir telli iletken (solid conductor)
rm: £ ok telli iletken (stranded conductor)