Cables | Halogen Free Flame Redundant cables

Halogen Free, Flame Retardant, XLPE Insulated Multi-Core Cables With Copper Conductor.

1

0.6/1 kV

 
 
1

Code
N2XH

Standards
VDE 0276

Technical Data
Max. operating temperature : 90 ° C
Max. short circuit temperature: 250 ° C
Rated voltage : 0.6/1 kV
Min. bending radius : 12 x D
D : Cable outer diameter

Application
These are cables with low dielectric losses used in energy networks in refineries, mines, hotels, schools, tunnels, high constructions, hospitals, power plant, data processing centers, business centers where there is a risk of fire.

Construction
1. Solid or stranded copper conductor
2. XLPE insulation
3. HFFR filler
4. HFFR outer sheath

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght
DC Conductor Resistance at 20 ° C
Current Carrying Capacity
in ground (20 ° C)
in air (30 ° C)

mm 2

mm

kg/km

m

ohm/km
A
A

4x1.5

12.0

200

1000

12.10

30

24

4x2.5

13.0

250

1000

7.41

40

32

4x4

14.0

300

1000

4.61

52

42

4x6

15.5

400

1000

3.08

64

53

4x10

17.5

580

1000

1.83

86

73

4x16

20.0

850

1000

1.15

111

96

4x25

24.5

1300

1000

0.727

143

130

4x35

26.0

1700

1000

0.524

173

160

4x50

30.0

2300

1000

0.387

205

195

4x70

34.0

3200

1000

0.268

252

247

4x95

38.0

4250

1000

0.193

303

305

4x120

43.0

5400

500

0.153

346

355

4x150

48.0

6600

500

0.124

390

407

4x185

53.0

8200

500

0.0991

441

469

4x240

61.0

10600

250

0.0754

511

551

4x300

67.0

13200

250

0.0601

580

638

4x400

76.0

16900

250

0.0470

663

746