Cables | Halogen Free Flame Redundant cables | |
Halogen Free, Flame Retardant, XLPE Insulated Multi-Core Cables With Copper Conductor. |
|
1 | |
0.6/1 kV |
|
1 | |
Code Standards Technical Data These are cables with low dielectric losses used in energy networks in refineries, mines, hotels, schools, tunnels, high constructions, 5 hospitals, power plant, data processing centers, business centers where there is a risk of fire. Construction
|
DIMENSIONS AND WEIGHTS |
ELECTRICAL PROPERTIES |
|||||
Nominal |
Overall Diameter (approx.) |
Net Weight (approx.) |
Delivery Lenght
|
DC Conductor Resistance at 20 ° C |
Current Carrying Capacity |
|
in ground (20 ° C) |
in air (30 ° C) |
|||||
mm 2 |
mm |
kg/km |
m |
ohm/km |
A |
A
|
3x16+10 |
20.0 |
800 |
1000 |
1.15 |
111 |
96 |
3x25+16 |
23.5 |
1200 |
1000 |
0.727 |
143 |
130 |
3x35+16 |
25.5 |
1500 |
1000 |
0.524 |
173 |
160 |
3x50+25 |
29.0 |
2100 |
1000 |
0.387 |
205 |
195 |
3x70+35 |
33.0 |
2900 |
1000 |
0.268 |
252 |
247 |
3x95+50 |
38.0 |
3900 |
1000 |
0.193 |
303 |
305 |
3x120+70 |
43.0 |
5000 |
500 |
0.153 |
346 |
355 |
3x150+70 |
47.0 |
5900 |
500 |
0.124 |
390 |
407 |
3x185+95 |
52.0 |
7500 |
500 |
0.0991 |
441 |
469 |
3x240+120 |
58.0 |
9500 |
500 |
0.0754 |
511 |
551 |
3x300+150 |
64.0 |
11800 |
250 |
0.0601 |
580 |
638 |
3x400+185 |
72.0 |
15000 |
250 |
0.0470 |
663 |
746 |