Cables | Halogen Free Flame Redundant cables

Halogen Free, Flame Retardant, Round Steel Wire Armoured, XLPE Insulated Multi-Core Cables With Copper Conductor.

1

0.6/1 kV

 
 
1

Code
N2XRH, CU/XLPE/SWA/LSF

Standards
VDE 0276, BS 6724

Technical Data
Max. operating temperature : 90 ° C
Max. short circuit temperature: 250 ° C
Rated voltage : 0.6/1 kV
Min. bending radius : 15 x D
D : Cable outer diameter

Application
These are cables with low dielectric losses used in energy networks in refineries, mines, hotels, schools, tunnels, high constructions, hospitals, power plant, data processing centers, business centers where there is a risk of fire.

Construction
1. Solid or stranded copper conductor
2. XLPE insulation
3. HFFR inner sheath
4. Galvanized round steel wires
5. Polyester tape
6. HFFR outer sheath

DIMENSIONS AND WEIGHTS

ELECTRICAL PROPERTIES

Nominal
Cross-Selection

Overall Diameter (approx.)

Net Weight (approx.)

Delivery Lenght
DC Conductor Resistance at 20 ° C
Current Carrying Capacity
in ground (20 ° C)
in air (30 ° C)

mm 2

mm

kg/km

m

ohm/km
A
A

3x1,5

13.5

290

1000

12.1

30

24

3x2,5

14.0

350

1000

7.41

40

32

3x4

15.5

420

1000

4.61

52

42

3x6

16.5

500

1000

3.08

64

53

3x10

20.0

900

1000

1.83

86

73

3x16

22.0

1150

1000

1.15

111

96

3x25

26.0

1700

1000

0.727

143

130

3x35

28.0

2100

1000

0.524

173

160

3x50

31.0

2700

1000

0.387

205

195

3x70

36.5

3800

1000

0.268

252

247

3x95

40.5

4700

1000

0.193

303

305

3x120

44.5

5700

500

0.153

346

355

3x150

50.0

7300

500

0.124

390

407

3x185

55.0

8800

500

0.0991

441

469

3x240

61.5

11000

250

0.0754

511

551