| Cables | Cables used in mining industry | |
| Power Cables for Mines | |
| 1 | |
| 3.8/6.6 kV | |
|  | |
| 1 | |
|   Application   General Structure  Construction   | |
|            Three Cores Double Layer Armoured Conductive Sheated 3800/6600 V Cables  | ||||||||
| Conductor Cross - Section | Inner Sheath Thickness | Overall Diameter of Inner Sheath | Diameter of Armour Wire | Number of Copper Armour Wire | Thickness of Sheath | App. Overall Diameter  | Current Capacity  | Rezistence of Armour  | 
| mm 2 | mm | mm | mm | mm | mm | Amp | ohm | |
| 16 | 1.4 | 31.0 | 1.6 | - | 2.1 | 44.0 | 94 | 1.530 | 
| 25 | 1.8 | 35.0 | 2.0 | - | 2.2 | 49.4 | 125 | 0.969 | 
| 35 | 1.8 | 37.5 | 2.0 | - | 2.3 | 52.3 | 150 | 0.699 | 
| 50 | 1.8 | 36.0 | 2.0 | - | 2.4 | 51.2 | 175 | 0.516 | 
| 70 | 1.8 | 39.5 | 2.0 | 2 | 2.5 | 54.5 | 220 | 0.357 | 
| 95 | 2.2 | 43.5 | 2.5 | 2 | 2.6 | 60.8 | 265 | 0.257 | 
| 120 | 2.2 | 46.0 | 2.5 | 5 | 2.7 | 63.7 | 305 | 0.204 | 
| 150 | 2.2 | 49.0 | 2.5 | 9 | 2.8 | 66.6 | 345 | 0.165 | 
| 185 | 2.6 | 53.0 | 2.5 | 15 | 2.9 | 70.8 | 390 | 0.132 | 
|           Three Cores Single Layer Armoured Conductive Sheated 3800/6600 V Cables  | ||||||||
| Conductor Cross - Section | Inner Sheath Thickness | Overall Diameter of Inner Sheath | Diameter of Armour Wire | Number of Copper Armour Wire | Thickness of Sheath | App. Overall Diameter  | Current Capacity  | Rezistence of Armour  | 
| mm 2 | mm | mm | mm | mm | mm | Amp | ohm | |
| 16 | 1.4 | 31.0 | 1.6 | 0 | 2.0 | 39.6 | 94 | 1.920 | 
| 25 | 1.8 | 35.0 | 2.0 | 0 | 2.1 | 44.2 | 125 | 1.210 | 
| 35 | 1.8 | 37.5 | 2.0 | 0 | 2.2 | 47.1 | 150 | 0.873 | 
| 50 | 1.8 | 36.0 | 2.0 | 3 | 2.2 | 45.8 | 175 | 0.645 | 
| 70 | 1.8 | 39.5 | 2.0 | 7 | 2.3 | 49.1 | 220 | 0.447 | 
| 95 | 2.2 | 43.5 | 2.5 | 7 | 2.5 | 54.6 | 265 | 0.322 | 
| 120 | 2.2 | 46.0 | 2.5 | 10 | 2.6 | 57.5 | 305 | 0.255 | 
| 150 | 2.2 | 49.0 | 2.5 | 13 | 2.7 | 60.2 | 345 | 0.207 | 
| 185 | 2.6 | 53.0 | 2.5 | 18 | 2.8 | 64.6 | 390 | 0.165 |